Carel AL65
Driver 1 autosetup not complete Driver 2autosetupnotcomplete Circuit 1 off AL66
Source: 030221501.pdf
What does Carel AL65 mean?
AL65 means Driver 1's autosetup procedure has not been completed. The autosetup is a mandatory commissioning step where the driver validates its configuration — including valve type, refrigerant, probe calibration, and system parameters — before it is allowed to regulate the expansion valve. Without completing autosetup, Driver 1 holds Circuit 1 offline indefinitely.
Symptoms
- Circuit 1 stays offline at startup regardless of operating conditions.
- AL65 is present from initial commissioning or after a parameter reset.
- Driver 1 may display an autosetup prompt on the controller interface.
- No superheat regulation occurs on Circuit 1.
Common causes
- Initial installation without completing the autosetup commissioning procedure.
- Controller parameters reset to factory defaults, clearing the autosetup completion flag.
- Incomplete autosetup due to incorrect probe or valve type selection during procedure.
- Power failure during the autosetup process before the completion flag was saved.
- Application software update that reset Driver 1 configuration.
Diagnostic steps
- 01
Navigate to the autosetup menu for Driver 1
From the pCO display, access the SYSTEM SET or AUTOSETUP menu and select Driver 1. Follow the on-screen guided procedure.
- 02
Configure refrigerant type and valve model
Select the correct refrigerant (e.g., R404A, R448A) and the expansion valve model installed on Circuit 1. Incorrect selections will cause control errors after autosetup completes.
- 03
Set probe types (S1 pressure and S2 temperature)
Confirm the ratiometric pressure probe model and NTC temperature probe are correctly specified in the Driver 1 parameters before running autosetup.
- 04
Complete the autosetup sequence
Run the full autosetup sequence. The controller will perform valve stepping tests and probe validation. Do not interrupt power during this process.
- 05
Reset AL65 and verify normal operation
After autosetup completes successfully, manually reset AL65. Circuit 1 will start regulating superheat once the go-ahead is issued.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL65 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If autosetup fails repeatedly or the controller cannot complete the sequence due to valve motor errors or probe faults, contact a Carel-authorized technician. Correct valve and refrigerant selection during autosetup is critical — incorrect configuration leads to chronic superheat alarms or compressor flooding and requires expert diagnosis.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com