Carel AL65 Error Code
Driver 1 autosetup not complete Driver 2autosetupnotcomplete Circuit 1 off AL66
Source: 030221501.pdf
What does Carel AL65 mean?
AL65 means Driver 1's autosetup procedure has not been completed. The autosetup is a mandatory commissioning step where the driver validates its configuration — including valve type, refrigerant, probe calibration, and system parameters — before it is allowed to regulate the expansion valve. Without completing autosetup, Driver 1 holds Circuit 1 offline indefinitely.
Symptoms
- Circuit 1 stays offline at startup regardless of operating conditions.
- AL65 is present from initial commissioning or after a parameter reset.
- Driver 1 may display an autosetup prompt on the controller interface.
- No superheat regulation occurs on Circuit 1.
Common causes
- Initial installation without completing the autosetup commissioning procedure.
- Controller parameters reset to factory defaults, clearing the autosetup completion flag.
- Incomplete autosetup due to incorrect probe or valve type selection during procedure.
- Power failure during the autosetup process before the completion flag was saved.
- Application software update that reset Driver 1 configuration.
Ask the AskWhiz AI about Carel AL65
AskWhiz
online
Diagnostic steps
Navigate to the autosetup menu for Driver 1
From the pCO display, access the SYSTEM SET or AUTOSETUP menu and select Driver 1. Follow the on-screen guided procedure.
Configure refrigerant type and valve model
Select the correct refrigerant (e.g., R404A, R448A) and the expansion valve model installed on Circuit 1. Incorrect selections will cause control errors after autosetup completes.
Set probe types (S1 pressure and S2 temperature)
Confirm the ratiometric pressure probe model and NTC temperature probe are correctly specified in the Driver 1 parameters before running autosetup.
Complete the autosetup sequence
Run the full autosetup sequence. The controller will perform valve stepping tests and probe validation. Do not interrupt power during this process.
Reset AL65 and verify normal operation
After autosetup completes successfully, manually reset AL65. Circuit 1 will start regulating superheat once the go-ahead is issued.
When to call a professional
If autosetup fails repeatedly or the controller cannot complete the sequence due to valve motor errors or probe faults, contact a Carel-authorized technician. Correct valve and refrigerant selection during autosetup is critical — incorrect configuration leads to chronic superheat alarms or compressor flooding and requires expert diagnosis.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com