Carel AL67 Error Code
Circuit 2 in Prevent mode Compressors off in circuit 2 Automatic 10 s
Source: 030221501.pdf
What does Carel AL67 mean?
AL67 means Circuit 2 is in Prevent mode, a protection state triggered when the condensing temperature or pressure exceeds a programmable prevention threshold. The controller stops all compressors on Circuit 2 and forces condenser fans to maximum speed to reduce condensing pressure. The alarm resets automatically within 10 seconds once conditions return to normal.
Symptoms
- All compressors on Circuit 2 shut off while condenser fans run at maximum speed.
- Controller display shows AL67 or Prevent status for Circuit 2.
- System capacity drops while Circuit 2 is in prevent mode.
- Automatic recovery occurs once condensing pressure drops below the prevent threshold differential.
Common causes
- High ambient temperature causing condensing pressure to exceed the prevent setpoint.
- Condenser coil fouled with dirt or debris, reducing heat rejection efficiency.
- Condenser fan motor failure reducing airflow across the coil.
- Refrigerant overcharge causing elevated condensing pressure.
- Airflow restriction at the condenser inlet or outlet (blocked discharge, recirculation).
Ask the AskWhiz AI about Carel AL67
AskWhiz
online
Diagnostic steps
Check condensing pressure or temperature reading
Read the Circuit 2 condensing pressure from the controller display. Confirm it is above the prevent setpoint and not a sensor false alarm.
Inspect condenser fans on Circuit 2
Verify all condenser fans for Circuit 2 are running and drawing correct amperage. A failed fan motor will prevent the system from recovering from Prevent mode.
Clean the condenser coil
Inspect the condenser coil for dirt buildup or debris blockage. Clean with coil cleaner and rinse according to the manufacturer's instructions.
Check for airflow recirculation
Ensure the unit installation allows free discharge of hot air and there is no recirculation path returning hot discharge air to the condenser inlet.
Review prevent setpoint configuration
Navigate to Circuit 2 protect parameters and verify the prevent setpoint is configured correctly for the installation design conditions.
When to call a professional
If Circuit 2 remains in Prevent mode despite clean coils and operating fans, or if condensing pressures are consistently elevated during normal ambient conditions, contact a licensed refrigeration technician to check refrigerant charge, condenser fan capacity, and system design. Repeated prevent mode events indicate an underlying system problem that requires professional evaluation.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com