Carel AL67
Circuit 2 in Prevent mode Compressors off in circuit 2 Automatic 10 s
Source: 030221501.pdf
What does Carel AL67 mean?
AL67 means Circuit 2 is in Prevent mode, a protection state triggered when the condensing temperature or pressure exceeds a programmable prevention threshold. The controller stops all compressors on Circuit 2 and forces condenser fans to maximum speed to reduce condensing pressure. The alarm resets automatically within 10 seconds once conditions return to normal.
Symptoms
- All compressors on Circuit 2 shut off while condenser fans run at maximum speed.
- Controller display shows AL67 or Prevent status for Circuit 2.
- System capacity drops while Circuit 2 is in prevent mode.
- Automatic recovery occurs once condensing pressure drops below the prevent threshold differential.
Common causes
- High ambient temperature causing condensing pressure to exceed the prevent setpoint.
- Condenser coil fouled with dirt or debris, reducing heat rejection efficiency.
- Condenser fan motor failure reducing airflow across the coil.
- Refrigerant overcharge causing elevated condensing pressure.
- Airflow restriction at the condenser inlet or outlet (blocked discharge, recirculation).
Diagnostic steps
- 01
Check condensing pressure or temperature reading
Read the Circuit 2 condensing pressure from the controller display. Confirm it is above the prevent setpoint and not a sensor false alarm.
- 02
Inspect condenser fans on Circuit 2
Verify all condenser fans for Circuit 2 are running and drawing correct amperage. A failed fan motor will prevent the system from recovering from Prevent mode.
- 03
Clean the condenser coil
Inspect the condenser coil for dirt buildup or debris blockage. Clean with coil cleaner and rinse according to the manufacturer's instructions.
- 04
Check for airflow recirculation
Ensure the unit installation allows free discharge of hot air and there is no recirculation path returning hot discharge air to the condenser inlet.
- 05
Review prevent setpoint configuration
Navigate to Circuit 2 protect parameters and verify the prevent setpoint is configured correctly for the installation design conditions.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL67 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If Circuit 2 remains in Prevent mode despite clean coils and operating fans, or if condensing pressures are consistently elevated during normal ambient conditions, contact a licensed refrigeration technician to check refrigerant charge, condenser fan capacity, and system design. Repeated prevent mode events indicate an underlying system problem that requires professional evaluation.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com