AL69Carel

Carel AL69 Error Code

Driver2 LANDisconnected O s (fixed) stable operation: Compressor 2 AL70 Built-in

Source: 030221426.pdf

What does Carel AL69 mean?

AL69 is the Driver 2 LAN Disconnected alarm on the Carel Standard Air-conditioner (030221426). The pCO controller has lost communication with EVD driver 2 on the pLAN network for more than the allowed timeout. Without a network connection, driver 2 cannot receive setpoint and control commands from the main controller, and circuit 2 may shut down or revert to digital input control only.

Symptoms

  • AL69 displayed on the controller.
  • Driver 2 NET LED on the EVD board is off or flashing, indicating a communication fault.
  • Circuit 2 compressor may shut down or operate at a fixed valve position depending on digital input status.
  • Alarm relay activates per configured relay output assignment.

Common causes

  • pLAN network cable between the pCO controller and EVD driver 2 disconnected or damaged.
  • Incorrect pLAN network address configured on driver 2 or the controller.
  • EVD driver 2 has powered off or lost its supply voltage.
  • Network communication cable too long or without proper termination.
  • Electromagnetic interference from nearby variable speed drives corrupting the pLAN signal.

Ask the AskWhiz AI about Carel AL69

AskWhiz bot

AskWhiz

online

Hi — I'm the Refrigeration demo. Ask me anything in this domain.

Diagnostic steps

  1. Inspect pLAN cable to EVD driver 2

    Check the tLAN/pLAN cable between the pCO controller and EVD driver 2. Reseat both connectors and inspect the cable for pinching, cuts, or loose terminal screws.

  2. Verify EVD driver 2 power supply

    Confirm driver 2 is powered by checking its indicator LEDs. Measure supply voltage at the driver 2 terminals and verify it is within the specified range for the driver model.

  3. Check network address configuration

    In the EVD driver 2 service menu, verify the network address is set correctly and does not conflict with other devices on the pLAN bus. Consult the Standard Air-conditioner application installation documentation for required addresses.

  4. Check cable routing for electromagnetic interference

    Ensure the pLAN cable is not routed adjacent to high-power conductors, inverter drive cables, or other electromagnetic interference sources. Reroute and shield if necessary.

  5. Power-cycle driver 2 and monitor recovery

    After correcting wiring or address issues, power-cycle EVD driver 2. Monitor the pCO alarm list to confirm AL69 clears and driver 2 communication is restored.

When to call a professional

If AL69 persists after verifying all wiring, power, and address settings, the EVD driver 2 board or the pCO input/output expansion for the LAN port may be faulty. Board-level replacement and re-commissioning of the network connection require Carel-authorized service personnel and manufacturer access credentials.