Carel AL77 Error Code
Driver 2 configuration not complete Compressor 2
Source: 030221426.pdf
What does Carel AL77 mean?
AL77 means the configuration of EVD Driver 2 is incomplete. The Carel Standard Air-Conditioners program requires the EVD expansion valve driver to have its essential parameters — refrigerant type, valve model, pressure probe type, and control mode — correctly set before it can manage Compressor Circuit 2. AL77 fires when the driver's commissioning setup is missing or contains invalid entries, causing Compressor 2 to shut down immediately.
Symptoms
- AL77 displayed on pCO terminal with Compressor 2 stopped immediately
- EVD Driver 2 display shows an incomplete commissioning state or default parameter values
- Circuit 2 non-functional; the driver will not attempt superheat control
Common causes
- EVD Driver 2 was replaced or factory-reset and has not been recommissioned
- Required configuration parameters (refrigerant, valve type, probe type, control mode) were not saved to the driver
- pLAN or tLAN communication loss during initial commissioning left the driver in an unconfigured state
- Firmware update on the EVD driver reset stored parameters to defaults
Ask the AskWhiz AI about Carel AL77
AskWhiz
online
Diagnostic steps
Access Driver 2 commissioning mode
Connect the CAREL display accessory (EVDIS00**0) to the EVD Driver 2. Navigate to the guided commissioning procedure, which prompts entry of the four key parameters in sequence.
Set refrigerant type
Select the refrigerant used in Circuit 2 from the driver's refrigerant list. Confirm the selection matches the system nameplate and the refrigerant loaded.
Configure valve model and pressure probe type
Enter the electronic expansion valve model number and select the pressure transducer type (ratiometric or 4–20 mA) connected to Driver 2 inputs S3 and S4.
Set the control mode
Select the main control mode (typically superheat control for standard refrigeration/AC applications). Save all parameters and confirm the driver exits the commissioning screen without errors.
Reset the alarm and verify restart
After completing commissioning, press ALARM on the pCO terminal to reset AL77. Compressor 2 should restart and Driver 2 should display live superheat values within a few minutes.
When to call a professional
If the driver repeatedly returns to an unconfigured state after commissioning, the EVD Driver 2 EEPROM is likely damaged. Board replacement and factory commissioning by a Carel-authorized technician is required. Also engage a professional if you are unsure which refrigerant, valve model, or control mode applies — incorrect entries can cause liquid slugging or compressor damage.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com