Carel AL77
Driver 2 configuration not complete Compressor 2
Source: 030221426.pdf
What does Carel AL77 mean?
AL77 means the configuration of EVD Driver 2 is incomplete. The Carel Standard Air-Conditioners program requires the EVD expansion valve driver to have its essential parameters — refrigerant type, valve model, pressure probe type, and control mode — correctly set before it can manage Compressor Circuit 2. AL77 fires when the driver's commissioning setup is missing or contains invalid entries, causing Compressor 2 to shut down immediately.
Symptoms
- AL77 displayed on pCO terminal with Compressor 2 stopped immediately
- EVD Driver 2 display shows an incomplete commissioning state or default parameter values
- Circuit 2 non-functional; the driver will not attempt superheat control
Common causes
- EVD Driver 2 was replaced or factory-reset and has not been recommissioned
- Required configuration parameters (refrigerant, valve type, probe type, control mode) were not saved to the driver
- pLAN or tLAN communication loss during initial commissioning left the driver in an unconfigured state
- Firmware update on the EVD driver reset stored parameters to defaults
Diagnostic steps
- 01
Access Driver 2 commissioning mode
Connect the CAREL display accessory (EVDIS00**0) to the EVD Driver 2. Navigate to the guided commissioning procedure, which prompts entry of the four key parameters in sequence.
- 02
Set refrigerant type
Select the refrigerant used in Circuit 2 from the driver's refrigerant list. Confirm the selection matches the system nameplate and the refrigerant loaded.
- 03
Configure valve model and pressure probe type
Enter the electronic expansion valve model number and select the pressure transducer type (ratiometric or 4–20 mA) connected to Driver 2 inputs S3 and S4.
- 04
Set the control mode
Select the main control mode (typically superheat control for standard refrigeration/AC applications). Save all parameters and confirm the driver exits the commissioning screen without errors.
- 05
Reset the alarm and verify restart
After completing commissioning, press ALARM on the pCO terminal to reset AL77. Compressor 2 should restart and Driver 2 should display live superheat values within a few minutes.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL77 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If the driver repeatedly returns to an unconfigured state after commissioning, the EVD Driver 2 EEPROM is likely damaged. Board replacement and factory commissioning by a Carel-authorized technician is required. Also engage a professional if you are unsure which refrigerant, valve model, or control mode applies — incorrect entries can cause liquid slugging or compressor damage.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com