Carel E10 Error Code
Serial probe S10 not updated OFF OFF automatic duty setting(c4) unchanged unchan
Source: 0300055EN.pdf
What does Carel E10 mean?
The E10 alarm on Carel ir33 and pCO controllers indicates that serial probe S10 has not been updated by the controller within the polling timeout period. S10 is part of the Carel serial probe network. When S10 communication fails, any control or alarm function dependent on this probe's reading falls back to duty-cycle operation controlled by parameter c4.
Symptoms
- E10 shown on the controller display alternating with temperature.
- S10-dependent control functions operate in duty-cycle fallback.
- Alarm relay and buzzer activate.
- The monitoring zone assigned to S10 has no live temperature readings.
Common causes
- Data cable break or short between the controller and the S10 probe.
- S10 probe power failure.
- Bus address conflict between S10 and another probe.
- S10 probe internal hardware failure.
Ask the AskWhiz AI about Carel E10
AskWhiz
online
Diagnostic steps
Locate the S10 probe and inspect cabling
Identify the physical S10 probe location. Inspect the bus cable, probe housing, and termination point for visible damage.
Verify power at S10
Measure supply voltage at the S10 probe terminals. Absence of supply indicates an upstream power wiring problem.
Confirm S10 bus address is unique
Review the address configuration for S10 and all other bus devices. Reconfigure if a duplicate is found.
Test bus continuity
With the system de-energized, use a multimeter to verify both RS-485 data lines are intact from controller to S10.
Replace S10 if confirmed faulty
If power, wiring, and address are correct but E10 persists, replace S10 with a compatible Carel serial probe and re-commission.
When to call a professional
If E10 persists after probe replacement or if multiple serial probes are simultaneously faulting, contact a Carel-authorized engineer. Controller communication bus hardware failures require professional diagnosis and component replacement that go beyond standard field maintenance and need specialized Carel service tooling.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: becoolrefrigeration.co.uk, www.carel.com