AskWhiz
E10Carel

Carel E10

Serial probe S10 not updated OFF OFF automatic duty setting(c4) unchanged unchan

Source: 0300055EN.pdf

Want this fix in your inbox? Full E10 guide + every Carel code, printable, free.

What does Carel E10 mean?

The E10 alarm on Carel ir33 and pCO controllers indicates that serial probe S10 has not been updated by the controller within the polling timeout period. S10 is part of the Carel serial probe network. When S10 communication fails, any control or alarm function dependent on this probe's reading falls back to duty-cycle operation controlled by parameter c4.

Symptoms

  • E10 shown on the controller display alternating with temperature.
  • S10-dependent control functions operate in duty-cycle fallback.
  • Alarm relay and buzzer activate.
  • The monitoring zone assigned to S10 has no live temperature readings.

Common causes

  • Data cable break or short between the controller and the S10 probe.
  • S10 probe power failure.
  • Bus address conflict between S10 and another probe.
  • S10 probe internal hardware failure.

Diagnostic steps

  1. 01

    Locate the S10 probe and inspect cabling

    Identify the physical S10 probe location. Inspect the bus cable, probe housing, and termination point for visible damage.

  2. 02

    Verify power at S10

    Measure supply voltage at the S10 probe terminals. Absence of supply indicates an upstream power wiring problem.

  3. 03

    Confirm S10 bus address is unique

    Review the address configuration for S10 and all other bus devices. Reconfigure if a duplicate is found.

  4. 04

    Test bus continuity

    With the system de-energized, use a multimeter to verify both RS-485 data lines are intact from controller to S10.

  5. 05

    Replace S10 if confirmed faulty

    If power, wiring, and address are correct but E10 persists, replace S10 with a compatible Carel serial probe and re-commission.

Keep this fix — get it by email with every Carel error code

A clean printable version of this Carel E10 guide + the full Carel code pack (130 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

If E10 persists after probe replacement or if multiple serial probes are simultaneously faulting, contact a Carel-authorized engineer. Controller communication bus hardware failures require professional diagnosis and component replacement that go beyond standard field maintenance and need specialized Carel service tooling.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Carel error codes

Sources: becoolrefrigeration.co.uk, www.carel.com