Carel E213
· electrical power not with the machine off and disconnected from mains power se
Source: 030222011.pdf
What does Carel E213 mean?
E213 on Carel heaterSteam humidifiers indicates that electrical power is not reaching the heating elements or pre-heater, or that the float is locked in the high-level position. The controller detects this condition at startup when no steam is produced and no current flows through the elements, despite the controller issuing a heating command. Manual reset is required after the fault is corrected.
Symptoms
- Humidifier does not produce steam at startup — elements are not energizing.
- E213 displayed on the controller.
- No current draw detected on the element power circuit.
- Float may be mechanically stuck at the high water level position.
Common causes
- Open circuit in the heating element power supply — blown fuse, open contactor, or tripped circuit breaker.
- Contactor or solid-state relay (SSR) failure preventing element energization.
- High-level float stuck in the raised position, signaling a full cylinder and blocking operation.
- Defective or open-circuit heating elements.
- Wiring fault in the element power or pre-heater circuit.
Diagnostic steps
- 01
Isolate power and inspect fuses and circuit breaker
With machine off and disconnected from mains, check all fuses in the heater circuit and the upstream circuit breaker. Replace blown fuses or reset tripped breakers after identifying and correcting the overload cause.
- 02
Check contactor and SSR operation
Verify the power contactor or solid-state relay energizes when commanded. Check for welded contacts, failed coil, or failed SSR output stage.
- 03
Inspect the high-level float for mechanical binding
Check the high-level float switch for scale buildup or physical obstruction holding it in the raised position. Clean or free the float mechanism.
- 04
Test heating element continuity
Measure resistance of each heating element with mains power disconnected. An open circuit (infinite resistance) indicates a failed element requiring replacement.
- 05
Follow the AR procedure and manually reset E213
After correcting the identified fault, execute the AR autotest retry procedure and then manually reset E213. Verify steam production resumes at startup.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel E213 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Diagnosing and replacing contactors, SSRs, and heating elements involves working with 230–400 V mains power. This work must be performed by a qualified electrician or licensed HVAC technician. Do not attempt to bypass safety interlocks or contactor controls to force element energization.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com