Carel E4 Error Code
Probe S4 fault OFF OFF automatic unchanged unchanged unchanged unchanged √ E5 Pr
Source: 0300055EN.pdf
What does Carel E4 mean?
The E4 alarm on Carel ir33 and pCO refrigeration controllers signals a fault on probe S4, the fourth temperature input. S4 is commonly configured as an additional evaporator probe, a product temperature probe, or a secondary zone sensor. When S4 fails, any control or alarm function relying on it is disabled, and the controller generates this alarm to notify the technician.
Symptoms
- E4 alternates with the temperature reading on the controller display.
- Control functions assigned to S4 — such as secondary zone alarms — are disabled.
- Alarm relay output activates.
- Auto-reset occurs once a valid probe signal returns.
Common causes
- Open-circuit in the S4 probe cable or sensor element.
- Short-circuit across the NTC probe element.
- Loose wiring at the S4 controller terminal.
- Incompatible probe type (PTC vs. NTC) connected to the S4 input.
Ask the AskWhiz AI about Carel E4
AskWhiz
online
Diagnostic steps
Check S4 terminal connections
Inspect the S4 terminal screws on the controller and confirm the probe wires are fully seated with the screws tight.
Measure probe resistance
Disconnect S4 and measure resistance. A healthy NTC at 20 °C reads approximately 10 kΩ; open-circuit or zero resistance confirms a failed probe.
Inspect the cable routing
Trace the S4 cable along its full path and look for damage, tight bends, or areas running adjacent to power cables.
Replace the probe
Install a compatible Carel NTC probe and connect securely to the S4 terminals. Ensure probe type matches the S4 input configuration.
Reset and verify
Power-cycle or reset the controller. Confirm E4 clears and S4 reads a plausible temperature value.
When to call a professional
Contact a qualified Carel technician if E4 persists after probe and wiring replacement, as the S4 analog input on the controller board may be damaged. Board replacement and full parameter recommissioning should only be performed by someone familiar with the Carel configuration environment.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: becoolrefrigeration.co.uk, www.carel.com