What does Carel E4 mean?

The E4 alarm on Carel ir33 and pCO refrigeration controllers signals a fault on probe S4, the fourth temperature input. S4 is commonly configured as an additional evaporator probe, a product temperature probe, or a secondary zone sensor. When S4 fails, any control or alarm function relying on it is disabled, and the controller generates this alarm to notify the technician.

Symptoms

  • E4 alternates with the temperature reading on the controller display.
  • Control functions assigned to S4 — such as secondary zone alarms — are disabled.
  • Alarm relay output activates.
  • Auto-reset occurs once a valid probe signal returns.

Common causes

  • Open-circuit in the S4 probe cable or sensor element.
  • Short-circuit across the NTC probe element.
  • Loose wiring at the S4 controller terminal.
  • Incompatible probe type (PTC vs. NTC) connected to the S4 input.

Diagnostic steps

  1. 01

    Check S4 terminal connections

    Inspect the S4 terminal screws on the controller and confirm the probe wires are fully seated with the screws tight.

  2. 02

    Measure probe resistance

    Disconnect S4 and measure resistance. A healthy NTC at 20 °C reads approximately 10 kΩ; open-circuit or zero resistance confirms a failed probe.

  3. 03

    Inspect the cable routing

    Trace the S4 cable along its full path and look for damage, tight bends, or areas running adjacent to power cables.

  4. 04

    Replace the probe

    Install a compatible Carel NTC probe and connect securely to the S4 terminals. Ensure probe type matches the S4 input configuration.

  5. 05

    Reset and verify

    Power-cycle or reset the controller. Confirm E4 clears and S4 reads a plausible temperature value.

Keep this fix — get it by email with every Carel error code

A clean printable version of this Carel E4 guide + the full Carel code pack (130 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Contact a qualified Carel technician if E4 persists after probe and wiring replacement, as the S4 analog input on the controller board may be damaged. Board replacement and full parameter recommissioning should only be performed by someone familiar with the Carel configuration environment.