Carel E406 Error Code
Discharge pressure probe fault or disconnected Disable Manual reset Closed E7 E4
Source: 030220563.pdf
What does Carel E406 mean?
E406 on Carel humiFog controllers signals that the discharge pressure probe is faulty or disconnected. The discharge pressure probe monitors system outlet pressure for safety. Without a valid reading, the controller enters Disable mode, suspending humidification output while keeping the unit in a safe state. Manual reset is required after the probe fault is corrected.
Symptoms
- Humidifier output is disabled — steam or fog production stops.
- E406 (or E6 on older display formats) is shown on the controller.
- Discharge pressure reading is absent or out of range on the display.
- Manual reset is required to restore operation after repair.
Common causes
- Damaged or disconnected wiring to the discharge pressure transducer.
- Failed pressure transducer (open circuit, short circuit, or out-of-range signal).
- Incorrect probe type configured in controller parameters.
- Moisture intrusion into the pressure transducer or its connector.
- Mechanical damage to the pressure probe fitting.
Ask the AskWhiz AI about Carel E406
AskWhiz
online
Diagnostic steps
Locate and inspect the discharge pressure probe
Identify the pressure transducer on the humidifier discharge line. Inspect the probe body, cable, and connector for visible damage, moisture, or loose connections.
Measure probe electrical signal
With power on, measure the probe output voltage or current at the controller input terminal. Verify it is within the expected range for the installed probe type (e.g., 4–20 mA or 0.5–4.5 V ratiometric).
Check parameter configuration for probe type
Navigate to the probe configuration parameters and confirm the selected probe type matches the physically installed transducer.
Replace the discharge pressure probe if faulty
Install a replacement probe of the correct type and pressure range. Use manufacturer-specified fittings and ensure proper sealing at the process connection.
Manually reset E406
After restoring a valid probe signal, manually reset the alarm by pressing the PRG/reset button. Verify humidifier output resumes normally.
When to call a professional
If the discharge pressure probe tests as functional but E406 persists, the controller input circuit may be defective. Probe replacement on a pressurized humidification system should be performed by a qualified technician with knowledge of system isolation, de-pressurization, and safe re-commissioning procedures.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com