Carel E422 Error Code
E424 Low room % rH High % rH from limit probe Warning Warning Automatic reset Au
Source: 030220563.pdf
What does Carel E422 mean?
E422 on Carel humiFog controllers is a low room relative humidity warning. The controller monitors the room humidity probe (or external controller signal) and raises E422 when measured humidity falls below the configured low limit threshold. This is a warning only — humidification continues and the alarm resets automatically when humidity returns above the threshold.
Symptoms
- E422 warning displayed on the controller.
- Room relative humidity reading is below the low limit setpoint.
- Humidifier remains operational; alarm is a signal-only warning.
- Alarm relay closes; automatic reset when humidity recovers.
Common causes
- Actual room humidity is genuinely low — high dry air infiltration or load conditions.
- Humidity probe (room sensor) is faulty, reading lower than actual conditions.
- Low humidity limit threshold set too high relative to actual design conditions.
- Humidifier capacity is undersized for the load, unable to maintain setpoint.
- Humidifier output is restricted by another active fault condition.
Ask the AskWhiz AI about Carel E422
AskWhiz
online
Diagnostic steps
Compare room humidity probe reading with a reference instrument
Use a calibrated handheld hygrometer to measure actual room humidity at the probe location. A large discrepancy indicates probe fault or incorrect installation.
Inspect the humidity probe location and wiring
Verify the probe is installed in a representative air sample location — not near air inlets, drafts, or localized heat sources — and that wiring connections are secure.
Check the low humidity alarm threshold parameter P3
Navigate to parameter P3 (low relative humidity alarm threshold) on the type H or T control module and confirm it is set appropriately for the application.
Verify humidifier output is not restricted
Confirm the humidifier is producing its rated steam output and no other active alarm is limiting production. Check steam pipe routing for blockages or excessive back-pressure.
When to call a professional
If E422 persists despite good probe readings and correct threshold settings, and the room remains consistently below target humidity, the humidifier may be undersized or improperly commissioned for the space. A licensed mechanical engineer or commissioning technician should evaluate system capacity, ductwork distribution, and setpoints.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com