Carel E422
E424 Low room % rH High % rH from limit probe Warning Warning Automatic reset Au
Source: 030220563.pdf
What does Carel E422 mean?
E422 on Carel humiFog controllers is a low room relative humidity warning. The controller monitors the room humidity probe (or external controller signal) and raises E422 when measured humidity falls below the configured low limit threshold. This is a warning only — humidification continues and the alarm resets automatically when humidity returns above the threshold.
Symptoms
- E422 warning displayed on the controller.
- Room relative humidity reading is below the low limit setpoint.
- Humidifier remains operational; alarm is a signal-only warning.
- Alarm relay closes; automatic reset when humidity recovers.
Common causes
- Actual room humidity is genuinely low — high dry air infiltration or load conditions.
- Humidity probe (room sensor) is faulty, reading lower than actual conditions.
- Low humidity limit threshold set too high relative to actual design conditions.
- Humidifier capacity is undersized for the load, unable to maintain setpoint.
- Humidifier output is restricted by another active fault condition.
Diagnostic steps
- 01
Compare room humidity probe reading with a reference instrument
Use a calibrated handheld hygrometer to measure actual room humidity at the probe location. A large discrepancy indicates probe fault or incorrect installation.
- 02
Inspect the humidity probe location and wiring
Verify the probe is installed in a representative air sample location — not near air inlets, drafts, or localized heat sources — and that wiring connections are secure.
- 03
Check the low humidity alarm threshold parameter P3
Navigate to parameter P3 (low relative humidity alarm threshold) on the type H or T control module and confirm it is set appropriately for the application.
- 04
Verify humidifier output is not restricted
Confirm the humidifier is producing its rated steam output and no other active alarm is limiting production. Check steam pipe routing for blockages or excessive back-pressure.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel E422 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If E422 persists despite good probe readings and correct threshold settings, and the room remains consistently below target humidity, the humidifier may be undersized or improperly commissioned for the space. A licensed mechanical engineer or commissioning technician should evaluate system capacity, ductwork distribution, and setpoints.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com