Carel F9 Error Code
Compressor 1 AL49 Driver 1 valve not closed during blackout Compressor 1 AL50 Dr
Source: 030221426.pdf
What does Carel F9 mean?
F9 in Carel pCO/EVD documentation refers to the EVD (electronic expansion valve driver) parameter for low superheat alarm delay — it is a configurable time parameter, not a standalone displayable alarm code. However, in the Standard Air-conditioners application (program code +030221426, source 030221426.pdf), alarm AL49 covers 'Driver 1 valve not closed during blackout' — meaning the EVD expansion valve driver for the first refrigerant circuit failed to close the electronic expansion valve when power was cut, leaving the valve in an open or unknown position. This creates a risk of liquid refrigerant flooding the compressor on restart.
Symptoms
- AL49 displayed on the pCO terminal (the alarm corresponding to this condition in the Standard Air-conditioners program).
- Manual reset is required to clear the alarm and resume circuit 1 operation.
- On restart after a power cut, the suction line may show frost or the compressor may be liquid slugging if the valve remained open.
- The EVD driver battery (if fitted) was not sufficient to close the valve during the blackout.
Common causes
- EVD driver battery discharged or absent — the battery is used to close the valve on power loss.
- Power interruption was too brief for the battery-backed valve close sequence to complete.
- Electronic expansion valve motor fault preventing the valve from reaching the fully-closed position.
- EVD driver firmware fault during the blackout shutdown sequence.
- Valve mechanism mechanically stuck, preventing closure when the driver commanded it.
Ask the AskWhiz AI about Carel F9
AskWhiz
online
Diagnostic steps
Inspect the EVD driver battery status
Access the EVD evolution or EVD4 driver connected to circuit 1. Check the battery status indicator or the driver display for a battery fault. If the battery is flat or absent, the driver cannot close the valve during a power loss — replace the battery before resetting.
Check EVD driver logs for associated alarms
Review the EVD driver's alarm history. Any valve motor error or EEPROM alarm alongside the blackout event indicates the driver itself was failing and contributed to the valve remaining open.
Verify the expansion valve position
If the driver display shows current valve opening percentage, confirm it reads 0 % (fully closed). If not, command a manual close from the driver service menu before attempting compressor restart.
Check for liquid return or compressor slugging on restart
If the valve was open during the outage, liquid may have migrated to the suction line. Before restarting, allow the circuit to equalise by monitoring pressures. Start the compressor cautiously and listen for liquid slugging (knocking).
Reset the alarm on the pCO terminal
Once the EVD driver battery is replaced or confirmed good and the valve is confirmed closed, press the Alarm reset key on the pCO terminal to clear the alarm. Monitor suction superheat during the first 10 minutes of operation.
When to call a professional
Contact a licensed refrigeration engineer if the compressor shows signs of liquid slugging after this alarm, or if the electronic expansion valve is suspected of mechanical failure. Refrigerant circuit diagnosis — including checking suction superheat, verifying valve operation, and assessing compressor condition — requires F-Gas certification and appropriate instrumentation. The EVD battery should be replaced on a scheduled basis per the Carel maintenance recommendation for the EVD driver series.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call