Manitowoc Ice SERVICE LIMIT 2
USE0050: long harvest cycle — 2 flashes of the service LED
Source: Manitowoc Ice/use0050a__man-use0050-sth111-th.pdf
What does Manitowoc Ice SERVICE LIMIT 2 mean?
On the USE0050, Service Limit 2 is the long-harvest fault, shown as 2 flashes of the service LED. If the maximum harvest time of 7 minutes is reached for 3 consecutive cycles, the machine shuts down and the power LED turns off.
Symptoms
- Machine off, power LED dark, 2 flashes on the service LED
- Harvests dragging to the timeout before the shutdown
- Ice slow to release from the evaporator
Common causes
- Closed or stuck bin switch
- Dirty (scaled) evaporator
- Refrigeration problem
- Electrical problem
Diagnostic steps
- 01
Confirm the code
Press the Service button and count 2 flashes.
- 02
Check the bin switch
A stuck-closed bin switch blocks normal harvest hand-off; test it first.
- 03
Descale the machine
Run the full descaling/sanitizing procedure — a dirty evaporator holds the ice slab.
- 04
Escalate to system diagnostics
If harvests still run long, follow the refrigeration diagnostics and wiring diagram checks.
Keep this fix — get it by email with every Manitowoc Ice error code
A clean printable version of this Manitowoc Ice SERVICE LIMIT 2 guide + the full Manitowoc Ice code pack (44 codes), straight to your inbox. Free.
When to call a professional
Refrigeration-system diagnosis and electrical work on this machine belong with a qualified commercial ice-machine technician (EPA certification for refrigerant work). If the service limit returns after the checks here, stop resetting the machine and book service — repeated safety-limit trips indicate an unresolved underlying fault.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Manitowoc Ice error codes
Safety Limit 1 - freeze cycle ran too long (long freeze)
SL#2Safety Limit 2 - harvest cycle ran too long (long harvest)
SL#3Safety Limit 3 - no water sensed during the freeze cycle
E01Long freeze cycle — freeze ran to the 60-minute limit; 6 consecutive trigger the SL#1 shutdown
E02Long harvest cycle — harvest hit the 3.5-minute limit; repeated events log SL#2
E03Input power loss recorded in the event log on power-up (event-log entry only, no alarm)
E04High condenser temperature — liquid line too hot (air- or water-cooled condenser fault)
E05High-pressure control opened — the HPCO safety switch tripped on excess discharge pressure
E07Starving TXV or low on charge — evaporator inlet/outlet (T3/T4) spread over 12°F, 10 consecutive checks
E08TXV fault (dual-circuit/single-evaporator models) — evaporator underfeed signature
E09Evaporator flooding, circuit 1 — early-freeze discharge temperature below the 6-cycle average
E10Evaporator flooding, circuit 2 (dual-TXV) — early-freeze discharge temperature below the 6-cycle average