Coreco dA
Dixell XW controller — door-open alarm
Source: Coreco_1592027610-xw60lt-xw60lrt-gb-r10-13022012_termostatos.pdf
What does Coreco dA mean?
On the Coreco controller (Dixell XW30/XW60/XW70), dA is the door-open alarm, raised by the door-switch digital input after the doA delay. When it clears, the compressor and fans restart per the rrd/odC settings.
Symptoms
- Display shows dA
- Buzzer sounds after the doA delay
- Rising cabinet temperature while the door is open
- Fans/compressor may stop while the door is open (per odC)
Common causes
- Door left open beyond the doA delay
- Door not closing fully / misaligned seal
- Door switch stuck or faulty
- Door-switch wiring fault
- Incorrect i1F/i2F door-switch or doA configuration
Diagnostic steps
- 01
Close the door
dA clears when the door is closed; shut the cabinet door fully and confirm the alarm clears and outputs restart.
- 02
Inspect the door and switch
Check the door closes and seals, and that the door switch reports closed when shut.
- 03
Check the door-input parameters
Verify the digital input is set as a door switch and the doA delay is appropriate.
Keep this fix — get it by email with every Coreco error code
A clean printable version of this Coreco dA guide + the full Coreco code pack (49 codes), straight to your inbox. Free.
When to call a professional
If the door is closed and the seal is sound but dA will not clear, the door switch or its wiring is likely faulty; have a qualified technician test/replace it. Electrical access is reserved for qualified personnel.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Coreco error codes
Control probe (probe 1) error — signal interrupted, short-circuited or incompatible probe
E1Evaporator / defrost probe (probe 2) error — signal interrupted, short-circuited or incompatible probe
E2Condenser / product probe (probe 3) error — signal interrupted, short-circuited or incompatible probe
IAImmediate or delayed alarm from the multifunction digital input (external alarm)
dOrOpen-door alarm from the door-switch digital input
LOLow-temperature alarm — measured temperature below set point by more than parameter AL
HIHigh-temperature alarm — measured temperature above set point by more than parameter AH
EEUnit parameter reading (data) error — saved configuration data error
EFOperating parameter reading (data) error — manual reset
EdDefrost ended by timeout — last defrost stopped on maximum duration, not on temperature
dFDefrost running — status message shown during a defrost cycle (not an alarm)
CHtDirty-condenser warning/alarm — pre-alarm (cht) between Ac-AE and Ac, then alarm (CHt) when Ac is exceeded and refrigeration stops (manual reset)