Coreco E7
Carel KDT-Touch controller — Keypad-to-power-board communication error
Source: Coreco_kdt-touch_instruction-sheet_9is24304-1_en_rel0613_termostatos.pdf
What does Coreco E7 mean?
On the Coreco controller (Carel KDT-Touch), E7 is keypad-to-power-board communication error: no communication between the keypad and the power board for 60 seconds or longer puts the KDT keypad into error mode E7; the keypad stays completely inactive except for the display showing the label E7, and clears once communication is restored.
Symptoms
- Display shows E7
- Keypad inactive except for the display
- No response to key presses
Common causes
- No communication between the keypad and the power board (>=60 s)
- Cable/connector fault between keypad and board
- Power-board fault
Diagnostic steps
- 01
Check the keypad-to-board connection
E7 is a keypad↔power-board communication error; check the connecting cable/connector. It clears once communication is restored.
Keep this fix — get it by email with every Coreco error code
A clean printable version of this Coreco E7 guide + the full Coreco code pack (49 codes), straight to your inbox. Free.
When to call a professional
If reseating the connection does not clear it, have a qualified technician check the keypad/power board.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Coreco error codes
Control probe (probe 1) error — signal interrupted, short-circuited or incompatible probe
E1Evaporator / defrost probe (probe 2) error — signal interrupted, short-circuited or incompatible probe
E2Condenser / product probe (probe 3) error — signal interrupted, short-circuited or incompatible probe
IAImmediate or delayed alarm from the multifunction digital input (external alarm)
dOrOpen-door alarm from the door-switch digital input
LOLow-temperature alarm — measured temperature below set point by more than parameter AL
HIHigh-temperature alarm — measured temperature above set point by more than parameter AH
EEUnit parameter reading (data) error — saved configuration data error
EFOperating parameter reading (data) error — manual reset
EdDefrost ended by timeout — last defrost stopped on maximum duration, not on temperature
dFDefrost running — status message shown during a defrost cycle (not an alarm)
CHtDirty-condenser warning/alarm — pre-alarm (cht) between Ac-AE and Ac, then alarm (CHt) when Ac is exceeded and refrigeration stops (manual reset)