Coreco HA2 Error Code
Dixell XW controller — condenser high-temperature alarm
Source: Coreco_1592027610-xw60lt-xw60lrt-gb-r10-13022012_termostatos.pdf
What does Coreco HA2 mean?
On the Coreco controller (Dixell XW30/XW60/XW70), HA2 is the condenser high-temperature alarm: the condenser probe has exceeded the Au2 limit after the Ad2 delay. What happens to the outputs depends on the AC2 parameter (compressor may be switched off).
Symptoms
- Display shows HA2
- Condenser running hot
- Compressor may switch off depending on AC2
Common causes
- Dirty or blocked condenser
- Restricted condenser airflow
- Failed or weak condenser fan
- High ambient temperature
Ask the AskWhiz AI about Coreco HA2
AskWhiz
online
Diagnostic steps
Clean the condenser
Clean the condenser coil and clear any airflow obstruction; HA2 means the condenser temperature exceeded the Au2 limit.
Check the condenser fan
Confirm the condenser fan runs and moves air.
Review AC2/Au2/Ad2
Verify the condenser-alarm parameters are set correctly for the unit.
When to call a professional
If cleaning the condenser and confirming the fan does not clear HA2, have a qualified refrigeration technician check the fan and sealed system; this work is reserved for qualified personnel.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Coreco documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Coreco Error Codes
Control probe (probe 1) error — signal interrupted, short-circuited or incompatible probe
Evaporator / defrost probe (probe 2) error — signal interrupted, short-circuited or incompatible probe
Condenser / product probe (probe 3) error — signal interrupted, short-circuited or incompatible probe
Immediate or delayed alarm from the multifunction digital input (external alarm)
Open-door alarm from the door-switch digital input
Low-temperature alarm — measured temperature below set point by more than parameter AL
High-temperature alarm — measured temperature above set point by more than parameter AH
Unit parameter reading (data) error — saved configuration data error
Operating parameter reading (data) error — manual reset
Defrost ended by timeout — last defrost stopped on maximum duration, not on temperature
Defrost running — status message shown during a defrost cycle (not an alarm)
Dirty-condenser warning/alarm — pre-alarm (cht) between Ac-AE and Ac, then alarm (CHt) when Ac is exceeded and refrigeration stops (manual reset)