Dixell XW controller — evaporator probe failure

Source: Coreco_1592027610-xw60lt-xw60lrt-gb-r10-13022012_termostatos.pdf

Want this fix in your inbox? Full P2 guide + every Coreco code, printable, free.

What does Coreco P2 mean?

On the Coreco controller (Dixell XW30/XW60/XW70), P2 is the evaporator probe failure alarm: the probe signal is interrupted, short-circuited or out of range so the controller can no longer read it. While P2 is active defrost cannot end on temperature and ends on time instead.

Symptoms

  • Display shows P2
  • Evaporator probe reading unavailable
  • Alarm/buzzer active and the alarm relay may energise
  • While P2 is active defrost cannot end on temperature and ends on time instead.

Common causes

  • Probe signal interrupted (open circuit / broken wire)
  • Probe short-circuited
  • Probe out of range or wrong (non-NTC/incompatible) type
  • Loose or corroded probe terminal
  • Faulty probe element

Diagnostic steps

  1. 01

    Confirm which probe failed

    The P-code identifies the failed probe (P1 thermostat, P2 evaporator, P3 configurable/display, P4 fourth probe). Note which one before testing.

  2. 02

    Inspect the probe wiring and connector

    With power isolated, check the affected probe's signal lead and terminal for an interrupted (open) or short-circuited connection and reseat any loose or corroded connector.

  3. 03

    Verify the probe type

    Confirm the fitted probe is the correct NTC type for the Dixell XW controller; an incompatible or out-of-range probe also raises the P-alarm.

  4. 04

    Replace the probe if faulty

    If the wiring is sound and the probe is the right type, replace it. The alarm clears automatically once the controller reads the probe correctly.

Keep this fix — get it by email with every Coreco error code

A clean printable version of this Coreco P2 guide + the full Coreco code pack (49 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Access to the cabinet's electrical parts is reserved for qualified personnel. If checking the wiring and connector does not clear the probe alarm, or the probe must be replaced and regulation re-verified, have a qualified refrigeration technician complete the work.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Coreco error codes