Coreco PA
Carel RTN400 controller — General pressure switch alarm (n = PEn, Manual Reset)
Source: Coreco_rtn400_instruction_sheet_9is24288-1_rel0413_en_termostatos.pdf
What does Coreco PA mean?
On the Coreco controller (Carel RTN400), PA is general pressure switch alarm (n = PEn, Manual Reset): activation of pressure switch alarm by general pressure switch; label PA displayed and recorded in folder ALr, alarm LED on, relay activated (if configured), regulation blocked; reset via rAP function.
Symptoms
- Display/record shows PA
- Regulation blocked while the alarm is active
- Pressure-switch input tripped
Common causes
- Refrigeration pressure outside limits (high or low)
- Dirty condenser / restricted airflow (high pressure)
- Low refrigerant charge or restriction (low pressure)
- Faulty pressure switch or wiring
Diagnostic steps
- 01
Identify the pressure fault
PA is a pressure-switch alarm. Determine whether it is high or low pressure and whether reset is automatic or manual.
- 02
Investigate the refrigeration cause
Check the condenser/airflow for high-pressure trips or charge/restriction for low-pressure trips.
Keep this fix — get it by email with every Coreco error code
A clean printable version of this Coreco PA guide + the full Coreco code pack (49 codes), straight to your inbox. Free.
When to call a professional
Pressure faults involve the sealed refrigeration system and must be diagnosed by a qualified refrigeration technician.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Coreco error codes
Control probe (probe 1) error — signal interrupted, short-circuited or incompatible probe
E1Evaporator / defrost probe (probe 2) error — signal interrupted, short-circuited or incompatible probe
E2Condenser / product probe (probe 3) error — signal interrupted, short-circuited or incompatible probe
IAImmediate or delayed alarm from the multifunction digital input (external alarm)
dOrOpen-door alarm from the door-switch digital input
LOLow-temperature alarm — measured temperature below set point by more than parameter AL
HIHigh-temperature alarm — measured temperature above set point by more than parameter AH
EEUnit parameter reading (data) error — saved configuration data error
EFOperating parameter reading (data) error — manual reset
EdDefrost ended by timeout — last defrost stopped on maximum duration, not on temperature
dFDefrost running — status message shown during a defrost cycle (not an alarm)
CHtDirty-condenser warning/alarm — pre-alarm (cht) between Ac-AE and Ac, then alarm (CHt) when Ac is exceeded and refrigeration stops (manual reset)